AMS for IN1 IN2 IN3 (pulses S0, analog value, digital value)

This FAQ describes how to set 2N® SmartCOM PRO ETH for AMS function. 2N® SmartCOM PRO can with this function automatically read data from the INPUTS and store data in the internal memory. This feature is available for all units with firmware 1.13.X


2N® SmartCOM PRO ETH is equipped with three inputs (IN1, IN2, IN3)

Input Interfaces:

  • Voltage range: 0–10 V DC
  • Current range: 0–20 mA DC
  • Digital input with threshold level setting
  • S0 pulse inputs (You can increase the S0 bus resistance against interference if necessary by connecting PullUp voltage from the power supply or an internal 3V6 supply)


Disconnect the 2N® SmartCom PRO from the power supply before opening the cover. Be careful while handling the jumpers to avoid damaging the device!


Make sure that the 2N® SmartCOM PRO ETH jumpers are set as shown in the following image


Pulse counting on S0 inputs

  • pulse counting on S0 inputs

at^scpulse1="start"                                               - enable pulse counting on input 1.
at^scams="ENABLE",1                                               - enable AMS functionality.
AT^SCAMS="DEV_ADD",128,"AIN_DIN","1/PULSE/ABS","5M"               - absolute value of pulses on input 1 each 5 minutes
at^scpulse2="start"                                               - enable pulse counting on input 2.
AT^SCAMS="DEV_ADD",128,"AIN_DIN","2/PULSE/REL","5M"               - relative (difference between two readouts) value of pulses on input 2 each 5 minutes
Possible time intervals:                                          -  "1M", "2M", "3M", "4M", "5M", "6M", "10M", "12M", "15M", "20M", "30M", "1H", "2H", "3H", "4H", "6H", "8H", "12H", "1D"


at^scams?                                                         - Show added devices
^SCAMS: 1> 128,"AIN_DIN","1/PULSE/ABS","5M"
^SCAMS: 2> 128,"AIN_DIN","2/PULSE/REL","5M"
AT^SCAMS="DEV_REMOVE",1                                           - Remove device from defined position

at^scdata="get_oldest",50
^SCDATA: "AMS",1461340261,12091,"AIN_DIN",1,0,"","131"           - results from port 1    
^SCDATA: "AMS",1461340381,12093,"AIN_DIN",1,0,"","228"           - results from port 1
^SCDATA: "AMS",1461340441,12094,"AIN_DIN",1,0,"","234"           - results from port 1
^SCDATA: "AMS",1461340681,12098,"AIN_DIN",2,0,"","21"            - results from port 2

Analog value on input

Calibrate 2N® SmartCOM PRO ETH inputs before measurement                               - Input circuit calibration

Current measurement:                              - range between 4 and 20 mA.

Voltage measurement:                              - range between 0 and 10V DC.

at^scams="ENABLE",1                                               - enable AMS functionality.
AT^SCAMS="DEV_ADD",128,"AIN_DIN","1/ADC/CAL","1M"                 - calibrated value will be store to memory (range  0 - 100) input 1
AT^SCAMS="DEV_ADD",128,"AIN_DIN","2/ADC/ABS","1M"                 - output from A/D converter will be stored to memory (range 0 - 1023) input 2
Possible time intervals:                                          - "1M", "2M", "3M", "4M", "5M", "6M", "10M", "12M", "15M", "20M", "30M", "1H", "2H", "3H", "4H", "6H", "8H", "12H", "1D"


at^scams?                                                         - Show added devices
^SCAMS: 1> 128,"AIN_DIN","1/ADC/CAL","1M"
^SCAMS: 2> 128,"AIN_DIN","2/ADC/ABS","1M"


AT^SCAMS="DEV_REMOVE",1                                            - Remove device from defined position


at^scdata="get_oldest",50

voltage was the same on both inputs - 6,45V                                                                      

^SCDATA: "AMS",1464185101,7112,"AIN_DIN",1,0,"","56"                - calibrated value on input 1
^SCDATA: "AMS",1464185101,7113,"AIN_DIN",2,0,"","521"               - output value from A/D on input 2

voltage was the same on both inputs - 4,45V 

^SCDATA: "AMS",1464185160,7114,"AIN_DIN",2,0,"","354"                - calibrated value on input 1
^SCDATA: "AMS",1464185160,7115,"AIN_DIN",1,0,"","38"                 - output value from A/D on input 2

voltage was the same on both inputs - 10,2V 

^SCDATA: "AMS",1464185221,7116,"AIN_DIN",1,0,"","92"                 - calibrated value on input 1
^SCDATA: "AMS",1464185221,7117,"AIN_DIN",2,0,"","848"                - output value from A/D on input 2

Digital value on input

Calibrate 2N® SmartCOM PRO ETH inputs before measurement                                      - Input circuit calibration

Current measurement:                                                 - range between 4 and 20 mA.
Voltage measurement:                                                 - range between 0 and 10V DC.
at^scams="ENABLE",1                                                  - enable AMS functionality.
AT^SCAMS="DEV_ADD",128,"AIN_DIN","2/DIN","1M"                        - digital value on input 2 will be stored in memory every minute
possible time intervals:                                              - "1M", "2M", "3M", "4M", "5M", "6M", "10M", "12M", "15M", "20M", "30M", "1H", "2H", "3H", "4H", "6H", "8H", "12H", "1D"

At^scams?
^SCAMS: 1> 128,"AIN_DIN","1/ADC/CAL","1M"
^SCAMS: 2> 128,"AIN_DIN","2/ADC/ABS","1M"                               
^SCAMS: 3> 128,"AIN_DIN","2/DIN","1M"                                - reading digital value on input 2 is on third position

AT^SCAMS="DEV_REMOVE",1                                             - Remove device from defined position

Voltage was 4,45V                                                                                                         - logical 0

^SCDATA: "AMS",1464186241,7150,"AIN_DIN",3,0,"","0"

^SCDATA: "AMS",1464186241,7151,"AIN_DIN",1,0,"","39"

^SCDATA: "AMS",1464186241,7152,"AIN_DIN",2,0,"","360"


Voltage was 6,45V                                                                                                         - logical 1

^SCDATA: "AMS",1464186301,7155,"AIN_DIN",3,0,"","1"

^SCDATA: "AMS",1464186301,7153,"AIN_DIN",1,0,"","56"

^SCDATA: "AMS",1464186301,7154,"AIN_DIN",2,0,"","524"



Direct read

one time readout, not stored to 2N® SmartCOM PRO internal memory

AT^SCAMS="DIRECT_READ",128,"AIN_DIN","1/ADC/CAL"                     - readout of current signal value on IN1, result is calibrated (range 0-100)
AT^SCAMS="DIRECT_READ",128,"AIN_DIN","2/DIN"                         - readout of current signal value on IN2 and this value is transformed to a logical value (range 0 - 1)
AT^SCAMS="DIRECT_READ",128,"AIN_DIN","1/PULSE/ABS"                   - read current count of pulses on IN1